LLC-BA Batch Unit Operation and Programming Manual 9 Input and Output Wiring Connections Make all connections to the LLC-BA from the back
LLC-BA Batch Unit Operation and Programming Manual 10 TERM 9 REL1NC is the normally closed contact for Relay 1. TERM 10 REL1NO is the
LLC-BA Batch Unit Operation and Programming Manual 11 1 mA increments with 5 – 13mA representing batch numbers 1-9. To assign the output
LLC-BA Batch Unit Operation and Programming Manual 12 Optional Hard Ground12-16VAC 300mA.Hot Center2010141516171912BATCH EXTERNAL F
LLC-BA Batch Unit Operation and Programming Manual 13 LLC-BA Initial Messages After five seconds the LLC-BA briefly displays ***AW Compa
LLC-BA Batch Unit Operation and Programming Manual 14 TOTALIZER 1 (TO1) In TOTALIZER 1 mode, the LLC-BA displays the total of the current
LLC-BA Batch Unit Operation and Programming Manual 15 Totalizer 1 Maintains a total of the batch currently running. In RUN Mode, a moment
LLC-BA Batch Unit Operation and Programming Manual 16 RUN Mode In the RUN Mode, the external batch functions inputs are active. (See the
LLC-BA Batch Unit Operation and Programming Manual 17 Use the BATCH key (SEL) and ENT to activate batches in PROGRAM mode. See Programmin
LLC-BA Batch Unit Operation and Programming Manual 18 Batch Progress Signal Directly corresponds to the progress of the batch where 4 mA
LLC-BA Batch Unit Operation and Installation Manual 1 Table of Contents Safety Definitions and Information ...
LLC-BA Batch Unit Operation and Programming Manual 19 Batch Function Timing Diagram
LLC-BA Batch Unit Operation and Programming Manual 20 AW Gear Meters Originally Programmed Values DELAY 00000.50 PRECUT 0000000. BATCH 1
LLC-BA Batch Unit Operation and Programming Manual 21 DELAY This variable sets the delay time for Relay2 (high flow solenoid output) rela
LLC-BA Batch Unit Operation and Programming Manual 22 situations (below 10Hz), the LLC-BA converts automatically to pulse-width measureme
LLC-BA Batch Unit Operation and Programming Manual 23 Remove the insignificant decimals often produced with this calculation as they resu
LLC-BA Batch Unit Operation and Programming Manual 24 KFT-Factor For the LLC to display in a desired engineering unit such as Gallons, t
LLC-BA Batch Unit Operation and Programming Manual 25 Decimal Point for KFT This variable selects the location of the decimal point in t
LLC-BA Batch Unit Operation and Programming Manual 26 To program a batch quantity, press the BATCH key (SEL). The display momentarily rea
LLC-BA Batch Unit Operation and Programming Manual 27 Limited Warranty AW Gear Meters warrants the product to be in good working o
LLC-BA Batch Unit Operation and Programming Manual 2 TO1 (REVERSE TOTAL 1) ...
LLC-BA Batch Unit Operation and Programming Manual 3 Decimal Point for KFT ...
LLC-BA Batch Unit Operation and Programming Manual 4 Safety Definitions and Information Do not attempt to install or use your AW Gear Met
LLC-BA Batch Unit Operation and Programming Manual 5 Quick Start Guide As with any precision-engineered device, always operate the LLC-B
LLC-BA Batch Unit Operation and Programming Manual 6 Use the SEL key to isolate the data you would like to enter. Use the UP and DN keys
LLC-BA Batch Unit Operation and Programming Manual 7 Depth = 132mm/5.2 inches; depth w/ flange = 139mm/5.5 inches Lexan® is a registe
LLC-BA Batch Unit Operation and Programming Manual 8 Dimensional Drawings