LLC-BA
OperaƟon & InstallaƟon Manual
Rev. 2
BATCH CONTROLLER
Vue de la page 0
1 2 3 4 5 6 ... 27 28

Résumé du contenu

Page 1 - BATCH CONTROLLER

LLC-BAOperaƟon & InstallaƟon ManualRev. 2BATCH CONTROLLER

Page 2

LLC-BA Batch Unit Operation and Programming Manual 9 Input and Output Wiring Connections Make all connections to the LLC-BA from the back

Page 3

LLC-BA Batch Unit Operation and Programming Manual 10 TERM 9 REL1NC is the normally closed contact for Relay 1. TERM 10 REL1NO is the

Page 4

LLC-BA Batch Unit Operation and Programming Manual 11 1 mA increments with 5 – 13mA representing batch numbers 1-9. To assign the output

Page 5 - Unpacking

LLC-BA Batch Unit Operation and Programming Manual 12 Optional Hard Ground12-16VAC 300mA.Hot Center2010141516171912BATCH EXTERNAL F

Page 6 - Quick Start Guide

LLC-BA Batch Unit Operation and Programming Manual 13 LLC-BA Initial Messages After five seconds the LLC-BA briefly displays ***AW Compa

Page 7 - Technical Data

LLC-BA Batch Unit Operation and Programming Manual 14 TOTALIZER 1 (TO1) In TOTALIZER 1 mode, the LLC-BA displays the total of the current

Page 8

LLC-BA Batch Unit Operation and Programming Manual 15 Totalizer 1 Maintains a total of the batch currently running. In RUN Mode, a moment

Page 9

LLC-BA Batch Unit Operation and Programming Manual 16 RUN Mode In the RUN Mode, the external batch functions inputs are active. (See the

Page 10 - LLC-BA Batch Unit

LLC-BA Batch Unit Operation and Programming Manual 17 Use the BATCH key (SEL) and ENT to activate batches in PROGRAM mode. See Programmin

Page 11

LLC-BA Batch Unit Operation and Programming Manual 18 Batch Progress Signal Directly corresponds to the progress of the batch where 4 mA

Page 12

LLC-BA Batch Unit Operation and Installation Manual 1 Table of Contents Safety Definitions and Information ...

Page 13 - LLC Input

LLC-BA Batch Unit Operation and Programming Manual 19 Batch Function Timing Diagram

Page 14 - Display Modes

LLC-BA Batch Unit Operation and Programming Manual 20 AW Gear Meters Originally Programmed Values DELAY 00000.50 PRECUT 0000000. BATCH 1

Page 15

LLC-BA Batch Unit Operation and Programming Manual 21 DELAY This variable sets the delay time for Relay2 (high flow solenoid output) rela

Page 16 - Operating Modes

LLC-BA Batch Unit Operation and Programming Manual 22 situations (below 10Hz), the LLC-BA converts automatically to pulse-width measureme

Page 17

LLC-BA Batch Unit Operation and Programming Manual 23 Remove the insignificant decimals often produced with this calculation as they resu

Page 18

LLC-BA Batch Unit Operation and Programming Manual 24 KFT-Factor For the LLC to display in a desired engineering unit such as Gallons, t

Page 19

LLC-BA Batch Unit Operation and Programming Manual 25 Decimal Point for KFT This variable selects the location of the decimal point in t

Page 20

LLC-BA Batch Unit Operation and Programming Manual 26 To program a batch quantity, press the BATCH key (SEL). The display momentarily rea

Page 21 - Programming the LLC-BA

LLC-BA Batch Unit Operation and Programming Manual 27 Limited Warranty AW Gear Meters warrants the product to be in good working o

Page 22

LLC-BA Batch Unit Operation and Programming Manual 2 TO1 (REVERSE TOTAL 1) ...

Page 23

LLC-BA Batch Unit Operation and Programming Manual 3 Decimal Point for KFT ...

Page 24

LLC-BA Batch Unit Operation and Programming Manual 4 Safety Definitions and Information Do not attempt to install or use your AW Gear Met

Page 25

LLC-BA Batch Unit Operation and Programming Manual 5 Quick Start Guide As with any precision-engineered device, always operate the LLC-B

Page 26 - Batch Programming

LLC-BA Batch Unit Operation and Programming Manual 6 Use the SEL key to isolate the data you would like to enter. Use the UP and DN keys

Page 27

LLC-BA Batch Unit Operation and Programming Manual 7  Depth = 132mm/5.2 inches; depth w/ flange = 139mm/5.5 inches Lexan® is a registe

Page 28 - Limited Warranty

LLC-BA Batch Unit Operation and Programming Manual 8 Dimensional Drawings